HV610 Series Hoisting-specific Frequency Converter
Low-voltage VFD
Model | hopePCS0500 | hopePCS0630 | ||
DC Parameters | DC Voltage Range | 500V~850V | 600V~850V | |
Max. DC Current | 1130A | 1147A | ||
AC Parameters | Charging and Discharging on grid mode | Rated Output Power | 500kW | 630kW |
Max. Output Power | 550kW | 693kW | ||
Rated Output Curren | 902A | 909A | ||
Max. Output Current | 992A | 1000A | ||
Rated Grid Voltage | 320V | 400V | ||
Operating Voltage Range | 256V~352V | 320V~440V | ||
Rated Grid Frequency | 50Hz / 60Hz | |||
Operating Frequency Range | ±3Hz | |||
THDi | <3% (Rated Power) | |||
DC Current Component | <0.5% (Rated Output Current) | |||
Power Factor | 1 (inductive)~1 (capacitive) | |||
Off-grid mode | Rated Output Power | 500kW | 630kW | |
Rated Output Voltage | 320V | 400V | ||
Rated Output Current | 902A | 909A | ||
Voltage Fluctuation Range | <10%, liner load, 100% change | |||
Output Voltage Distortion | <3%, liner load | |||
Rated Grid Frequency | 50Hz / 60Hz | |||
Voltage Regulation Accuracy | <1% | |||
System Parameters | Max. Efficiency | 98.90% | 99.00% | |
Isolation Transformer | without | |||
Standby Power Consumption | <50W | |||
Cooling Method | Forced air cooling | |||
Protection Class | IP20 | |||
Operating Temperature Range | -40℃~+55℃ (Operation with derating above 40℃) | |||
Storage Temperature Range | -40℃~+70℃ | |||
Operating Altitude | ≤6000m (Operation with derating above 2000m) | |||
Relative Humidity | 0%~95%, no condensation | |||
Communication | RS485, Ethernet, CAN | |||
Mechanical Parameters | Dimensions (W*H*D) | 1000*2150*800mm | ||
Weight | 800kg |