Turnkey PCS Station
Customized design 6kV~35kV full-range customization 1MW~6.9MW customization Customizable dry-type transformer and oil transformer
Performance characteristics
Multiple parallel machines supported
Parallel operation function on the AC side of multiple PCSs
Dual power redundancy design
Reliable auxiliary power supply, with the control power supply to support dual power redundancy design
High protective performance
Protection grade IP54 and anti-corrosion grade C4 of the whole cabin
Strong adaptability to the power grid
High and low voltage ride-through capacity to support the grid with full reactive power and improve power quality
Various complete schemes
Various configuration schemes to meet the users’ different needs
Customized design
6kV~35kV full-range customization 1MW~6.9MW customization Customizable dry-type transformer and oil transformer
main parameters
ModelHPPS-2000HPPS-2500AHPPS-2500BHPPS-2750HPPS-3000HPPS-3450
AC ParametersAC Access ModeThree-phase three wire
Rated  Power2000kW2500kW2750kW3000kW3450kW
Short-term Overload Capacity110% load: 10min; 120%load: 1min
Boost Output Voltage6kV / 10kV / 35kV
Type of Transformer VentilationCombine/Split
Rated grid Frequency50Hz
Frequency Range±3Hz
THD<3% 
Power Factor>0.99 (20%Load)
Power Factor Adjustable Range1 (inductive)~1 (capacitive)
DC ParametersRated Power 2000kW2500kW2750kW3000kW3450kW
Max. Continuous power2200kW2750kW3025kW3300kW3795kW
Short-term Overload Capacity2400kW3000kW3300kW3600kW4140kW
DC Voltage range600V~850V1000V~1440V
Max. Long operating current916A*41146A*41375A*21512A*21650A*21879A*2

Protection ClassIP54
Noise75dB
Operating Temperature Range -30℃~+55℃ 
Storage temerature Range -40℃~+65℃
Cooling MethodForced air cooling
Relative Humidity0%~95%, no condensation
Communication InterfaceEthernet, Optical, RS485
Control System Power SupplySelf-powered / Externally powered