Model | HSNV100K-G01 | HSNV110K-G01 |
DC Input | ||
Max. Input Voltage | 1100 V | |
Starting Voltage | 180 V | |
MPPT Voltage Range | 200~1000 V | |
Max. Input Current Per MPPT | 65 A / 65 A / 65 A / 65 A | |
Max. Short-circuit Current | 100 A / 100 A / 100 A / 100 A | |
Number of DC Inputs | 5 / 5 / 5 / 5 | |
Number of MPP Trackers | 4 | |
AC Output | ||
Rated Output Power | 100 kW | 110 kW |
Max. Output Power | 110 kW | 121 kW |
Rated Output Voltage | 230 V / 400 V (3P + N + PE) | |
Operating Voltage Range | 300~520 V | |
Rated Output Current | 144.3 A | 158.8 A |
Max. Output Current | 158.8 A | 174.7 A |
Rated Grid Frequency | 50 Hz / 60 Hz | |
Power Factor | >0.99 (0.8 leading~0.8 lagging) | |
Harmonic (THDi) | <3% (at rated power) | |
Efficiency | ||
Max. Efficiency | 98.60% | |
European Efficiency | 98.30% | |
Protection | ||
PV Reverse Polarity Protection | Yes | |
Insulation Impedance Detection | Yes | |
Residual Leakage Current Detection | Yes | |
Output Overcurrent Protection | Yes | |
Anti-Islanding Protection | Yes | |
DC Surge Protection | Type II | |
AC Surge Protection | Type II | |
I/V Curve Scanning | Yes | |
Zero Export Function | Yes | |
PV String Monitoring | Yes | |
Arc Fault Circuit Interrupter (AFCI) | Optional | |
PID Recovery | Optional | |
DC Switch | Yes | |
General Parameters | ||
Dimensions (W × H × D) | 800 × 690 × 330 mm | |
Weight | ≤94 kg | |
Ingress Protection | IP65 | |
Operating Temperature Range | -40~+60℃ | |
Cooling System | Smart air cooling | |
Topology | Transformerless | |
Operating Altitude | 4000 m (>3000 m derating) | |
Display | LED, WLAN + APP | |
Communication | RS485 / Wi-Fi | |
DC Connection Type | MC4 | |
AC Connection Type | OT / DT terminal | |
Standard Compliance (More Available Upon Request) | ||
Certification | IEC 62109, IEC 61000, IEC 61727, IEC 62116, IEC 60068, IEC 61683, EN 50549-1, EN 50549-2, VDE 4105, VDE 4110, VDE 4120 |