Capacity | 20MVA~150MVA | |
Rated Voltage | AC35kV±10% | |
Input Frequency | Adjustable from 0.1 Hz/s to 50 Hz/s | |
Allowed Grid Voltage THD (Normal Operation) | ≤4% | |
Allowed Grid Voltage Unbalance (Normal Operation) | ≤4% | |
Steady-State Output Voltage | 0% to 140%, Accuracy ≤ 0.2% | |
High Voltage Ride-Through (HVRT) Output | 110% to 140%, Response time ≤ 10ms | |
Low Voltage Ride-Through (LVRT) Output | 0% to 90%, Response time ≤ 10ms | |
Continuous HVRT/LVRT Output | Supports 2 to 6 consecutive ride-through events | |
Output Frequency | 45 Hz to 66 Hz, Accuracy ≤ 0.01 Hz | |
Three-Phase Voltage Unbalance | 1% to 15%, Accuracy ≤ 0.1% | |
Output Flicker | Pst: 1 to 10, Accuracy ≤ 0.1 | |
Output Harmonics/Interharmonics | 2 to 50 times, Accuracy ≤ ±0.3% | |
Primary Frequency Regulation (PFR) | Adjustable from 0.1 Hz/s to 50 Hz/s | |
Inertia Response | Adjustable from 0.1 Hz/s to 50 Hz/s | |
Impedance Scanning | 1~2000 | |
Load Simulation | For independent load operation, black start, and transition between grid-following and grid-forming modes | |
Grid Strength Adaptability | SCR:1~10 | |
Phase Angle Jump | -90°~90° | |
Low-Frequency Oscillation Adaptability | Oscillation Frequency: 0.1 Hz to 2.5 Hz | |
Noise | ≤85dB | |
System Efficiency | ≥95% | |
Lightning Protection | Yes | |
Fire Detection, Monitoring & Protection | Yes | |
Parallel Operation Function | Supports parallel operation of 6 or more units. | |
Cooling Mode | Air-Cooled | |
Altitude | 2000m | |
Layout / Arrangement | Indoor | Containerized |
Protection Rating | IP23 | Operation:IP23 |
Standby:IP54 | ||