HPPS Series 7.5MW String PCS Turnkey Station
Customizable MV voltage level of 6~35kV
Performance characteristics
Small Footprint
7.5MW within Standard 40ft container to reduce floor space
Rack-level Management
Rack-level management for batteries to address the issue of circulating current in parallel connections
Modular Design
Modular design to prevent single point of failure, easy maintenance
Safe and Reliable
Strong environmental adaptability with C4~C5 anti-corrosion degree available, and no derating at 45°C
Customised Design
Flexible capacity configuration and customizable MV voltage level of 6~35kV
Comprehensive Functions
PQ, VF, VSG operating modes with grid-forming function
main parameters
ModelHPPS-7500B
DC Parameters
Number of DC Input Channels36
Max. DC Current281A*36
DC Voltage Operating Range1000~1500V
AC Parameters
Total Rated Power7500kW
Max. Output Power8250kVA
Rated Voltage690Vac
Isolation ModeTransformer Isolation
Reactive Power Range0~7875kvar
On-grid Mode
Rated Grid Voltage6~35kV (customizable)
Rated Grid Frequency50Hz / 60Hz
THDi<3%
Power Factor-1~1
Transformer Parameters
Rated Capacity7700kVA
Transformer TypeOil-immersed Transformer
LV/MV Voltage0.69 / 0.69 / (6~35) kV
System Parameters
Dimensions (W*H*D)12192*2896*2438mm
Operating Temperature-40~+60℃ (derating above 45℃)
Operating Humidity0~100%
Operating Altitude≤4000m (no derating within 3000m)
Protection DegreeIP54 (PCS IP66)
Communication ProtocolModbus TCP / IEC 61850 / IEC 104 / Modbus RTU / CAN 2.0
Standard CompliancePCS: GB/T 34120-2023, IEC 62477-1, IEC 61000-3/-6, EN 50549-1/-2/-10, IEC60068-2, G99, VDE 4110/4120, NTS 2.1, IEC TS 62910, etc.
MV Transformer:  IEC 60076(Please contact Hopewind team for latest certifications)
Grid SupportH/LVRT, frequency adjustment function, voltage adjustment function, inertia response, etc.
*The table only lists some models. Products can be customized for projects.

*Please refer to the latest physical product for any changes in specifications.


download